Perform the setting change or removal for indoor unit

The setting change or removal can be performed for indoor unit.

NOTES:

  • The operation mode and Airflow Direction, Fan Speed, and other display contents may be different depending on the unit (model).
  • For the function which is not supported by the indoor unit, the button is inactive.
Start-up
  1. Select link image (a) on “Outdoor Unit Setting” screen.

"Indoor Unit Settings" (General) window
  1. Select the "General" menu (1).
  2. Enter the following page information.
  3. To complete the setting, select the button (4).
    The setting will be saved, and the window will close.

    NOTE: When operation is performed and reflected at a unit, always select the button (4).
    If the settings are not sent, operation will not be reflected at the unit.
    When the system is special situation such as maintenance or the setting is limited, even if the setting is performed, it is not reflected in the indoor unit.

If you want to close the window without saving the changes, select the button (2).

(a) Enter the indoor unit name.

(b) Model name is displayed.

(c) Enter the serial No.

(d) Refrigerant system address is displayed.

(e) The indoor unit address is displayed.

(f) Operation Stop/Start

(g) Filter Icon
 After cleaning the air filters, select this button to reset the filter status.
 Check the confirmation message and select [OK]. The filter status is reset.

(h) Set the temperature setpoint.

NOTES:

  • Custom Auto:
    Set the set temperature for cooling and the set temperature for heating separately. During the Custom Auto mode operation, when the room temperature exceeds the set temperature for cooling, the cooling operation is performed, and when the room temperature falls below the set temperature for heating, the heating operation is performed. (It can be used only when the setting of the indoor unit compatible with this function is valid.)
  • The settable temperature range is different for each operation mode.
    Settable temperature range
    Cool/Dry* 18 to 30 °C (64 to 88 °F) or 20 to 30 °C (68 to 88 °F)
    Heat 10 to 30 °C (48 to 88 °F)
    Custom Auto Same as the above range, but there are temperatures that can not be set due to the deadband.
    Auto* 18 to 30 °C (64 to 88 °F) or 20 to 30 °C (68 to 88 °F)
    The lower limit of the setting temperature is different depending on the place of use.
    The heating set temperature range of 10°C to 15°C (48°F to 58°F) may not be settable, depending on the indoor unit model.
    Celsius display increases and decreases in 0.5°C steps and Fahrenheit display increases and decreases in 1°F steps.
  • Deadband:
    The deadband is the minimum value of the difference between the set temperature for cooling and the set temperature for heating (= cooling set temperature - heating set temperature) in Custom Auto mode.
    The difference between the set temperature for cooling and heating in Custom Auto mode can not be smaller than the deadband. The deadband is set in the indoor unit. To change this, consult an authorized service personnel.

(i) Select the operating mode.

NOTE: When the operation mode is set while its setting is limited, it is not reflected in the indoor unit even if saved. If the changed setting is not reflected in the operation mode, confirm that the operation mode is active.

(j) Economy On/Off
 It automatically saves more electricity by changing the set temperature to a moderate setting.

Cooling/Dry mode Higher up to 4°C than the set temperature
Heating mode Lower up to 2°C than the set temperature

 The set temperature shown on the screen remains the temperature before moderating.

(k) Anti-Freeze On/Off

(2) [CANCEL] button

(3) [DELETE UNIT] button
 Deletes the indoor unit information.

NOTE: When indoor units are deleted, only indoor units are deleted.
When remote controller groups are included, always delete by the whole remote controller group.
You can delete the indoor unit only when the indoor unit status is Offline.

(4) [SAVE] button
 Saves the indoor unit information.

NOTES:

  • In "Fan" operation section, airflow switching steps are different depending on the indoor unit type to be operated.
    For details, refer to the indoor unit operation manual.
  • Anti-Freeze is a function that performs low temperature heating operation to prevent freezing of water lines and equipment, when air conditioning operation is off, in regions where outside temperature may drop below freezing.
    If water lines are far from the unit or within exterior walls, this function may not provide enough anti-freeze protection.
  • ”Filter Sign” indicates the air filter cleaning interval set at the indoor unit.
    Reset the sign when the filter was cleaned.
"Indoor Unit Settings" (Airflow) window
  1. Select the "Airflow" menu (1).
  2. Enter the following page information.
  3. To complete the setting, select the button (4).
    The setting will be saved, and the window will close.

    NOTE: When operation is performed and reflected at a unit, always select the button (4).
    If the settings are not sent, operation will not be reflected at the unit.
    When the system is special situation such as maintenance or the setting is limited, even if the setting is performed, it is not reflected in the indoor unit.

If you want to close the window without saving the changes, select the button (2).

(a) Select the airflow mode.

NOTE: When the mode is "Fan", only "Auto" can be set for the airflow.

(b) Select the Vertical louver position.

(c) Select the Horizontal louver position.

(d) [Configuration] button
 Moves to the "Individual Airflow - Configuration".
 When the individual airflow is set, "Activated" will be shown above this button.

(2) [CANCEL] button

(3) [DELETE UNIT] button
 Deletes the indoor unit information.

NOTE: When indoor units are deleted, only indoor units are deleted.
When remote controller groups are included, always delete by the whole remote controller group.
You can delete the indoor unit only when the indoor unit status is Offline.

(4) [SAVE] button
 Saves the indoor unit information.

"Individual Airflow - Configuration" window

Set the indoor unit air direction individually.

(a) Select the vertical louver position setting.

(b) Select the horizontal louver position setting.

(c) [Cancel] button

(d) [Save] button
 Saves the Individual Airflow settings.

NOTES:

  • When changing the individual airflow settings, save the settings on both this window and "Indoor Unit Settings" window.
  • When clearing the individual airflow settings, select "Not Set".
"Indoor Unit Settings" (Temperature Limits) window
  1. Select the "Temperature Limits" menu (1).
  2. Enter the following page information.
  3. To complete the setting, select the button (4).
    The setting will be saved, and the window will close.

    NOTE: When operation is performed and reflected at a unit, always select the button (4).
    If the settings are not sent, operation will not be reflected at the unit.
    When the system is special situation such as maintenance or the setting is limited, even if the setting is performed, it is not reflected in the indoor unit.

If you want to close the window without saving the changes, select the button (2).

(a) Temperature Limits On/Off
  Activates/Deactivates the Custom temperature limit settings.

NOTES:

  • Set the upper and lower limit temperatures settings to the registered indoor unit.
  • The temperature settings from the Standard Remote Controllers are restricted.
  • When the temperature setting range is restricted by “Temperature Limit” setting of the indoor unit registered in Zone, the temperature setpoint setting range that can be set in "Zone Functions" is also restricted in the same way.

(b) Temperature limits at Cool

(c) Temperature limits at Dry

(d) Temperature limits at Heat

(e) Temperature limits at Auto
  Items of Temperature Limits at Auto differ depending on the function information of selected indoor unit. When indoor unit of Dual setpoint is selected, Auto Cool and Auto Heat are displayed at Setpoint Limits. When indoor unit of Single setpoint is selected, only Auto single setpoint is displayed at Setpoint Limits.

NOTES:

  • Setpoint Limits which have been set is reflected to the Devices and limit the Setpoint according to the operation mode set at General tab.    
  • When other VRF central control devices such as Touch Panel Controller (UTY-DTGYZ1), and System Controller (UTY-APGXZ1), etc. are in the VRF system, the functions may conflict. In such cases, do not limit the temperature range from other devices.

(2) [CANCEL] button

(3) [DELETE UNIT] button
 Deletes the indoor unit information.

NOTE: When indoor units are deleted, only indoor units are deleted.
When remote controller groups are included, always delete by the whole remote controller group.
You can delete the indoor unit only when the indoor unit status is Offline.

(4) [SAVE] button
 Saves the indoor unit information.

"Indoor Unit Settings" (Occupancy Sensor Settings) window
  1. Select the "Temperature Limits" menu (1).
  2. Enter the following page information.
  3. To complete the setting, select the button (4).
    The setting will be saved, and the window will close.

    NOTE: When operation is performed and reflected at a unit, always select the button (4).
    If the settings are not sent, operation will not be reflected at the unit.
    When the system is special situation such as maintenance or the setting is limited, even if the setting is performed, it is not reflected in the indoor unit.

If you want to close the window without saving the changes, select the button (2).

(a) Auto Economy On/Off

(b) Set the time.

(c) Auto On/Off On/Off (supported in the future)

(d) Set the time. (supported in the future)

NOTE: "Auto On/Off" and "Auto Off" cannot be used at the same time. Either of them is disabled.

The relationship among "Auto Economy" absence detection time, "Auto On/Off", and "Auto Off" absence detection time setting is shown below.
"Auto Economy" absence detection time < "Auto On/Off" absence detection time
"Auto Economy" absence detection time < "Auto Off" absence detection time

(e) Auto Off On/Off

(f) Set the time.

(2) [CANCEL] button

(3) [DELETE UNIT] button
 Deletes the indoor unit information.

NOTE: When indoor units are deleted, only indoor units are deleted.
When remote controller groups are included, always delete by the whole remote controller group.
You can delete the indoor unit only when the indoor unit status is Offline.

(4) [SAVE] button
 Saves the indoor unit information.

"Indoor Unit Settings" (RC Prohibition (Lockout)) window
  1. Select the "Temperature Limits" menu (1).
  2. Enter the following page information.
  3. To complete the setting, select the button (4).
    The setting will be saved, and the window will close.

    NOTE: When operation is performed and reflected at a unit, always select the button (4).
    If the settings are not sent, operation will not be reflected at the unit.
    When the system is special situation such as maintenance or the setting is limited, even if the setting is performed, it is not reflected in the indoor unit.

If you want to close the window without saving the changes, select the button (2).

(a) All operations are prohibited.

(b) Timer setting is prohibited.

(c) Setpoint setting is prohibited.

(d) Operation mode setting is prohibited.

(e) Start/Stop Operation is prohibited.

(f) Start Operation is prohibited.

(g) Filter Reset Operation is prohibited.

NOTE: The function which can be set here has the following contents.

R.C. Prohibition Contents
All Operation of all control functions are enabled or disabled.
On/Off “On/Off” operation is enabled or disabled.
On “On” operation is enabled or disabled.
Temp. “Temperature setting” operation is enabled or disabled.
Mode “Operation mode setting” is enabled or disabled.
Timer “Timer setting” operation of remote controller is enabled or disabled.
Filter “Filter reset” operation is enabled or disabled.

(2) [CANCEL] button

(3) [DELETE UNIT] button
 Deletes the indoor unit information.

NOTE: When indoor units are deleted, only indoor units are deleted.
When remote controller groups are included, always delete by the whole remote controller group.
You can delete the indoor unit only when the indoor unit status is Offline.

(4) [SAVE] button
 Saves the indoor unit information.