Schedule settings

The Schedules can be set for selected Zones.
The maximum numbers of Schedules and Programs are shown in the following table.

Item Max. number of registration
Schedule 4 (per 1 Zone)
Program 12 (per 1 Schedule)

NOTE: When setting the Schedule in the “Bulk edit zones” screen, all current Schedules are deleted.

Add Schedule settings
  1. Select [+ADD] or [ADD SCHEDULE] button (a) on the "BULK EDIT ZONES" screen.
    The "Add Schedule" window appears.

    [+ADD] button (When no schedule is set) [ADD SCHEDULE] button (When any schedule is set)

  2. Enter the schedule information in (b) to (c).
  3. Select (e).
    The window closes and the schedule is added.

    If you want to close the window without adding a schedule, select the button (d).

    (b) Schedule Name Enter the schedule name.
    (c) Start Date/End Date Set the period to apply the schedule.


Add Operation programs
  1. Select the menu (a) of the Schedule to which you add operation programs.
  2. Select the [ADD PROGRAM] button (b).


Edit Operation programs
  1. Enter the details on the operation program in (a) to (i).

(a) On/Off button

To activate the program, set this button to "On."

To deactivate the program, set this button to "Off."

(b) Menu button To delete the program, select "DELETE PROGRAM" from the menu.
(c) Day of the week Select the day of the week to which this program is applied.
(d) Program name Enter the program name.
(e) Start Time Set the time when this program starts.
(f) [AUTO OFF] button

To activate the Auto-Off Timer, set the "Auto Off" to [On] and set the time to Auto-Off Operation from here.

The Auto-Off Timer stops the operation when any indoor units in the Zones have been operating for the set time.

If the operation status changes, the countdown for Auto-Off Timer is reset.

(g) Zone Functions

Zone Function Set the operation mode and temeprature of Theraml ZFC
And/Or, Set the airflow volume, setpoint and operation mode of Ventilation ZFC
For details, refer to "Zone function settings"

NOTES:

  • When Start/Stop, operation mode setting, room temp. setting, fan speed setting, airflow direction setting, swing setting, economy mode, and anti-freeze setting are changed frequently by using the central controller like BMS, System controller, Touch panel controller, etc., the number of operations for each indoor unit must not exceed 7,500 times/year.
    If the number of setting changes exceeds the above specified number, the rewriting frequency of the EEPROM (built into the air conditioner and used for setting memory) will be exceeded and may cause a breakdown.
  • If it is determined that the setting of cooling set temperature and heating set temperature is out of deadband value, the operation setting will not be sent.
  • When multiple users operate this system at the same time, more items than the above table can be registered.
    If you use this system with such a condition, we do not guarantee the proper operation of the AIRSTAGE Edge Controller and the connected device.
  • When the operation mode is set while its setting is limited, it is not reflected in the indoor unit even if saved. If the changed setting is not reflected in the operation mode, confirm that the operation mode is active.
Schedule Exceptions (Overrides)

If you want to set the other schedules during the scheduled period, set Schedule Exceptions (Overrides).

The setting procedure is similar to "Edit operation programs" above.

The maximum number of Schedule exceptions is shown in the following table.

Item Max. number of registration
Schedule exception 24 (per 1 Zone)

NOTES:

  • The Schedule Exceptions are applied every day during the period. The day of the week to which the setting is applied cannot be selected.
  • When multiple users operate this system at the same time, more items than the above table can be registered. In such a case, we do not guarantee the proper operation of the AIRSTAGE Edge Controller and the connected devices.