Slim Duct Slim & Comfort ARXG09KLLAP

Indoor unit, Remote controller, Outdoor unit

ALL DC V-PAM
Indoor Unit :
ARXG09KLLAP
Outdoor Unit :
AOYG09KBTB
Download :
Catalogue

Features

  • Slim design
  • Compact and lightweight outdoor unit
  • Selectable with a wide range of static pressure
  • Auto Louver Grille Kit (Option)
  • Low ambient operation

Feature Explanation Icons

Economy mode : Thermostat setting automatically changes according to the temperature to avoid unnecessary cooling and heating. Auto-changeover : The unit automatically switches between heating and cooling modes based on your temperature setting and the room temperature. Automatic fan speed : The micro-computer automatically adjusts the airflow effectively to follow the changes of room temperature. Auto restart : In the event of a temporary power failure, the air conditioner will automatically restart in the same operating mode as before, once power supply is restored. Weekly + setback timer : Weekly + Setback timer can set temperature for two times spans and for each day of the week. Filter sign : Indicates the filter cleaning period by lamp. Drain pump as standard

Capacity

Cooling   2.5 kW
Heating   3.2 kW


Specification

Power source Phase Single-phase
Voltage 230 V
Frequency 50 Hz
Capacity Cooling 2.5 (0.9 - 3.2) kW
Heating 3.2 (0.9 - 4.7) kW
Input Power Cooling 0.600 kW
Heating 0.790 kW
EER Cooling 4.17 W/W
COP Heating 4.05 W/W
Pdesign Cooling 2.5 kW
Heating (-10°C) 2.6 kW
SEER Cooling 6.20 W/W
SCOP Heating (Average) 4.30 W/W
Energy Efficiency Class Cooling A++
Heating (Average) A+
Max. Operating Current Cooling 7.9 A
Heating 7.9 A
Annual Energy Consumption Cooling 141 kWh/a
Heating 845 kWh/a
Moisture Removal 0.7 l/h
Sound Pressure Level Indoor (Cooling) High 28 dB(A)
Middle 27 dB(A)
Low 26 dB(A)
Quiet 25 dB(A)
Indoor (Heating) High 28 dB(A)
Middle 26 dB(A)
Low 25 dB(A)
Quiet 24 dB(A)
Sound Pressure Level Outdoor (Cooling) High 46 dB(A)
Outdoor (Heating) High 46 dB(A)
Sound Power Level Indoor (Cooling) High 57 dB(A)
Indoor (Heating) High 57 dB(A)
Outdoor (Cooling) High 59 dB(A)
Outdoor (Heating) High 59 dB(A)
Air Flow Rate Indoor (Cooling) High 600 m3/h
Outdoor (Cooling) High 1480 m3/h
Static pressure range (Standard) 0 - 90 (25) Pa
Net Dimensions
Indoor
Height 198 mm
Width 700 mm
Depth 620 mm
Net Dimensions
Outdoor
Height 542 mm
Width 799 mm
Depth 290 mm
Net Weight Indoor 17.0 kg
Outdoor 32.0 kg
Connection Pipe Diameter Liquid φ6.35 mm
Gas φ9.52 mm
Drain Hose Diameter φ25(I.D.), φ32(O.D.) mm
Max Pipe Length (Pre Charge) 20 (15.0) m
Max Height Difference 15 m
Operation Range Cooling -15 to 46 °CDB
Heating -15 to 24 °CDB
Refrigerant Type R32
Global Warming Potential 675
Charge 850 g (0.574 CO2eq–T)
Scroll

Dimensions

Indoor Unit : ARXG09KLLAP

Indoor unit