Automatic fan speed: Microprocessor automatically adjusts the fan speed and airflow according to changes in room temperature. Auto restart: The unit automatically restarts in the previous operation mode when power returns after an outage. Auto changeover: The unit automatically switches between heating and cooling operations based on the set temperature and room temperature. Connectable distributing duct: Supplied branch ducts can be attached to better distribute airflow. Connectable fresh air duct: Takes in outside air by attaching a supplied duct to the fresh air knockout and an optional part. Economy mode: A thermostat setting is adjusted automatically according to the room temperature to avoid unnecessary cooling or heating. Weekly & Temperature setback timer: Sets temperature for two sets of On/Off times and for each day of the week. Filter sign: Indicates when the filter should be cleaned.

Capacity

Cooling  13.4 kW
Heating  16.0 kW

Recommended static pressure : 30 - 200


Specification

Power source Phase Single-phase
Voltage 220 V
Frequency 50 Hz
Capacity Cooling 45,700 BTU/h (15,400 - 49,500) BTU/h
Heating 54,600 BTU/h (16,000 - 56,000) BTU/h
Cooling 13.4 kW(4.5 - 14.5) kW
Heating 16.0 kW (4.7 - 16.5) kW
Input Power Cooling 4.42 kW
Heating 4.62 kW
EER Cooling 3.03 W/W
COP Heating 3.46 W/W
Pdesign Cooling - kW
Heating (-10°C) - kW
Max. Operating Current Cooling 23.5 A
Heating 23.5 A
Running Current Cooling 19.4 A
Heating 20.2 A
Moisture Removal 3.7 I/h
Sound Pressure Level Indoor (Cooling) High 39 dB(A)
Middle 35 dB(A)
Low 31 dB(A)
Quiet 29 dB(A)
Indoor (Heating) High 39 dB(A)
Middle 35 dB(A)
Low 31 dB(A)
Quiet 29 dB(A)
Sound Pressure Level Outdoor (Cooling) High 57 dB(A)
Outdoor (Heating) High 57 dB(A)
Sound Power Level Indoor (Cooling) High 67 dB(A)
Indoor (Heating) High 69 dB(A)
Outdoor (Cooling) High 69 dB(A)
Outdoor (Heating) High 71 dB(A)
Air Flow Rate Indoor High 2550 m3/h
Outdoor High 6750 m3/h
Static pressure range (Standard) 30 to 200 (60) Pa
Net Dimensions
Indoor
Height 300 mm
Width 1400 mm
Depth 700 mm
Net Dimensions
Outdoor
Height 1290 mm
Width 900 mm
Depth 330 mm
Net Weight Indoor 46 kg
Outdoor 86 kg
Connection Pipe Diameter Liquid 9.52 mm
Gas 15.88 mm
Drain Hose Diameter Indoor 25 mm
Outdoor 32 mm
Max Pipe Length (Pre Charge) 50 (20) m
Max Height Difference 30 m
Operation Range Cooling -15 to 46 °CDB
Heating -15 to 24 °CDB
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 3,350 g
Scroll
* :
That specification is not fixed yet.

Dimensions

Indoor Unit : ARYG54LHTBP

Indoor unit

Optional Parts

Wired Remote Controller
UTY-RNNYM
Simple Remote Controller
UTY-RSNYM
Flange
UTD-RF204 (Round)
Flange
UTD-SF045T (Square)
Long-life Filter
UTD-LF25NA
Remote Sensor Unit
UTY-XSZX
External Connect Kit
UTY-XWZXZ2
External Connect Kit
UTY-XWZXZ3
External Control Set
UTD-ECS5A
Drain Pump Unit
UTZ-PX1NBA
IR Receiver Kit
UTY-LRHY1
IR Receiver Kit
UTY-LRHYM