Heat Pump Modular Type V-III Series AJY324LALBH [3Phase]
Features
- Excellent energy saving
- Great design flexibility for placement in any building
- Easy installation and maintenance
- Outstanding efficiency in real-world operating conditions
- Energy-saving technologies for boosting operational efficiency
Capacity
Specification
| Rated Capacity Range | 36 |
|---|---|
| Maximum Connectable Indoor Unit | 64 |
| Indoor unit connectable capacity | 50.0 - 135.0 kW |
Scroll
| Power source | Phase | 3-phase 4 wire |
|---|---|---|
| Voltage | 400 V | |
| Frequency | 50 Hz | |
| Capacity | Cooling | 100.0 kW |
| Heating | 100.0 kW | |
| Input Power | Cooling | 33.12 kW |
| Heating | 27.26 kW | |
| EER | Cooling | 3.02 W/W |
| COP | Heating | 3.67 W/W |
| Air Flow Rate | 13,700×2 m³/h | |
| Sound Pressure Level*2 | Cooling | 66 dB(A) |
| Heating | 67 dB(A) | |
| Sound Power Level | Cooling | 87 dB(A) |
| Heating | 89 dB(A) | |
| Max. External Static Pressure | 82 Pa | |
| Compressor Motor Output | 11.0×2 kW | |
| Heat exchanger fin | Blue fin | |
| Net Dimensions | Height | 1,690 mm |
| Width | 1,240×2 mm | |
| Depth | 765 mm | |
| Net Weight | 275×2 kg | |
| Refrigerant | Type | R410A |
| Global Warming Potential | 2,088 | |
| Charge | 11.8×2 kg | |
| Connection Pipe Diameter | Liquid | 19.05 mm |
| Gas | 41.27 mm | |
| Operation Range | Cooling | -5 to 46 °CDB |
| Heating | -20 to 21 °CDB | |
Scroll
- Note:
- Specifications are based on the following conditions.
- Cooling:
- Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
- Heating:
- Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
- Pipe length:
- 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
- When cooling operation will be conducted at outdoor air temperature below -5°C,
- the outdoor unit must be installed in a position that is higher than or equal to those of indoor units.
- *1
- Minimum connectable indoor unit number is 2.
- *2
- The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
- surrounding noise and reflections are received and the measured value is usually larger than the indicated value.
Dimensions
Outdoor Unit : AJY162LALBH / AJY162LALBH