Capacity

Cooling  28.0 kW
Heating  31.5 kW

Specification

Rated Capacity Range 10
Maximum Connectable Indoor Unit 16
Indoor unit connectable capacity 14.0 - 42.0 kW
Scroll
Power source Phase 3-phase 4 wire
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 28.0 kW
Heating 31.5 kW
Input Power Cooling 7.11 kW
Heating 7.33 kW
EER Cooling 3.94 W/W
COP Heating 4.30 W/W
Air Flow Rate 11,100 m³/h
Sound Pressure Level Cooling 58 dB(A)
Heating 59 dB(A)
Sound Power Level Cooling 79 dB(A)
Heating 81 dB(A)
Max. External Static Pressure 80 Pa
Compressor Motor Output 7.5 kW
Heat exchanger fin Blue fin
Net Dimensions Height 1,690 mm
Width 930 mm
Depth 765 mm
Net Weight 262 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.8 kg
Connection Pipe Diameter Liquid 12.70 mm
Discharge Gas 19.05 mm
Suction Gas 22.22 mm
Operation Range Cooling -10 to 46 °CDB
Heating -20 to 21 °CDB
Cooling / Heating -10 to 21 °CDB
Scroll
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.