Heat Recovery Modular Type VR-II Series AJY378GALH  [3Phase]

Outdoor unit

Outdoor Unit :
AJY144GALH
Outdoor Unit :
AJY144GALH
Outdoor Unit :
AJYA90GALH
Download :
Catalogue

Features

  • Highly energy-efficient operation
  • Energy-saving technologies for boosting operational efficiency
  • Ideal heat-exchanging path control
  • Sophisticated operation control
  • Flexible piping connection
  • Flexible installation of an RB Unit

Capacity

Cooling  118.0 kW
Heating  131.5 kW

Specification

Rated Capacity Range 42
Maximum Connectable Indoor Unit 63
Indoor unit connectable capacity 59.0 - 177.0 kW
Scroll
Power source Phase 3-phase 4 wire
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 118.0 kW
Heating 131.5 kW
Input Power Cooling 34.33 kW
Heating 32.87 kW
EER Cooling 3.44 W/W
COP Heating 4.00 W/W
Air Flow Rate 13,000×2+11,100 m³/h
Sound Pressure Level Cooling 65 dB(A)
Heating 65 dB(A)
Sound Power Level Cooling 86 dB(A)
Heating 87 dB(A)
Max. External Static Pressure 80 Pa
Compressor Motor Output 11.0×2+7.5 kW
Heat exchanger fin Blue fin
Net Dimensions Height 1,690 mm
Width 1,240×2+930 mm
Depth 765 mm
Net Weight 286×2+262 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.8×3 kg
Connection Pipe Diameter Liquid 19.05 mm
Discharge Gas 34.92 mm
Suction Gas 41.27 mm
Operation Range Cooling -10 to 46 °CDB
Heating -20 to 21 °CDB
Cooling / Heating -10 to 21 °CDB
Scroll
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.

Dimensions

Outdoor Unit : AJY144GALH / AJY144GALH / AJYA90GALH

Outdoor unit