Heat Recovery Modular Type VR-II Series AJY144GALH [3Phase]
Features
- Highly energy-efficient operation
- Energy-saving technologies for boosting operational efficiency
- Ideal heat-exchanging path control
- Sophisticated operation control
- Flexible piping connection
- Flexible installation of an RB Unit
Capacity
Specification
| Rated Capacity Range | 16 |
|---|---|
| Maximum Connectable Indoor Unit | 24 |
| Indoor unit connectable capacity | 22.5 - 67.5 kW |
Scroll
| Power source | Phase | 3-phase 4 wire |
|---|---|---|
| Voltage | 400 V | |
| Frequency | 50 Hz | |
| Capacity | Cooling | 45.0 kW |
| Heating | 50.0 kW | |
| Input Power | Cooling | 13.61 kW |
| Heating | 12.77 kW | |
| EER | Cooling | 3.31 W/W |
| COP | Heating | 3.92 W/W |
| Air Flow Rate | 13,000 m³/h | |
| Sound Pressure Level | Cooling | 61 dB(A) |
| Heating | 61 dB(A) | |
| Sound Power Level | Cooling | 82 dB(A) |
| Heating | 83 dB(A) | |
| Max. External Static Pressure | 80 Pa | |
| Compressor Motor Output | 11.0 kW | |
| Heat exchanger fin | Blue fin | |
| Net Dimensions | Height | 1,690 mm |
| Width | 1,240 mm | |
| Depth | 765 mm | |
| Net Weight | 286 kg | |
| Refrigerant | Type | R410A |
| Global Warming Potential | 2,088 | |
| Charge | 11.8 kg | |
| Connection Pipe Diameter | Liquid | 12.70 mm |
| Discharge Gas | 22.22 mm | |
| Suction Gas | 28.58 mm | |
| Operation Range | Cooling | -10 to 46 °CDB |
| Heating | -20 to 21 °CDB | |
| Cooling / Heating | -10 to 21 °CDB | |
Scroll
- *1
- Minimum connectable indoor unit number is 2.
- *2
- The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
- surrounding noise and reflections are received and the measured value is usually larger than the indicated value.
Dimensions
Outdoor Unit : AJY144GALH

GLOBAL | English