Heat Pump Modular Type V-III Series AJY450LALBH [3Phase]
- Outdoor Unit :
- AJY162LALBH
- Outdoor Unit :
- AJY144LALBH
- Outdoor Unit :
- AJY144LALBH
- Download :
-
Catalogue
Features
- Excellent energy saving
- High design flexibility for various building air conditioning
- Easy installation and maintenance
- Efficiency in actual operation
- Energy saving technology that boosted operation efficiency
Capacity
Specification
| Rating Capacity Range | 50 |
|---|---|
| Maximum Connectable Indoor Unit*1 | 64 |
| Indoor unit connectable capacity | 70.0 - 202.5 kW |
Scroll
| Power source | Phase | 3-phase 4 wire |
|---|---|---|
| Voltage | 400 V | |
| Frequency | 50 Hz | |
| Capacity | Cooling | 140.0 kW |
| Heating | 150.0 kW | |
| Input Power | Cooling | 42.58 kW |
| Heating | 40.89 kW | |
| EER | Cooling | 3.29 W/W |
| COP | Heating | 3.67 W/W |
| Air Flow Rate | 13,700×3 m/³h | |
| Sound Pressure Level*2 | Cooling | 67 dB(A) |
| Heating | 69 dB(A) | |
| Sound Power Level | Cooling | 88 dB(A) |
| Heating | 91 dB(A) | |
| Maximum external static pressure | 82 Pa | |
| Compresor motor output | 11.0×3 kW | |
| Heat exchanger fin | Blue fin | |
| Net Dimensions | Height | 1,690 mm |
| Width | 1,240×3 mm | |
| Depth | 765 mm | |
| Net Weight | 275×3 kg | |
| Refrigerant | Type | R410A |
| Global Warming Potential | 2,088 | |
| Charge | 11.8×3 kg | |
| Connection Pipe Diameter | Liquid | 19.05 mm |
| Gas | 41.27 mm | |
| Operation Range | Cooling | -5 to 46 °CDB |
| Heating | -20 to 21 °CDB | |
Scroll
- Note:
- Specifications are based on the following conditions.
- Cooling:
- Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
- Heating:
- Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
- Pipe length:
- 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
- When cooling operation will be conducted at outdoor air temperature below -5°C,
- the outdoor unit must be installed in a position that is higher than or equal to those of indoor units.
- *1
- Minimum connectable indoor unit number is 2.
- *2
- The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
- surrounding noise and reflections are received and the measured value is usually larger than the indicated value.
Dimensions
Outdoor Unit : AJY162LALBH / AJY144LALBH / AJY144LALBH