Heat Pump Modular type V-III TROPICAL Series AJY342LNLBH [3Phase]
- Outdoor Unit :
- AJY162LNLBH
- Outdoor Unit :
- AJY090LNLBH
- Outdoor Unit :
- AJY090LNLBH
- Download :
-
Catalogue
Features
- Excellent energy saving
- Great design flexibility for placement in any building
- Easy installation and maintenance
- Energy-saving technologies for boosting operational efficiency
- Thorough anti-corrosion treatment
- Outstanding cooling capacity
Capacity
Specification
| Rated Capacity Range | 38 |
|---|---|
| Maximum Connectable Indoor Unit | 55 |
| Indoor unit connectable capacity | 53 - 137.8 kW |
Scroll
| Power source | Phase | 3-phase |
|---|---|---|
| Voltage | ~400 V | |
| Frequency | 50,60 Hz | |
| Capacity | Cooling | 106.0 kW |
| Heating | 113.0 kW | |
| Input Power | Cooling | 31.12 kW |
| Heating | 28.13 kW | |
| EER | Cooling | 3.41 W/W |
| COP | Heating | 4.02 W/W |
| Air Flow Rate | 13700+11100×2 m³/h | |
| Sound Pressure Level | Cooling | 65 dB(A) |
| Heating | 66 dB(A) | |
| Sound Power Level | Cooling | 86 dB(A) |
| Heating | 88 dB(A) | |
| Max. External Static Pressure | 82 Pa | |
| Compressor Motor Output | 11.0+7.5×2 kW | |
| Heat exchanger fin | Blue fin | |
| Net Dimensions | Height | 1690×3 mm |
| Width | 1240+930×2 mm | |
| Depth | 765×3 mm | |
| Net Weight | 279+255×2 kg | |
| Refrigerant | Type | R410A |
| Global Warming Potential | 2,088 | |
| Charge | 11.8+11.7×2 kg | |
| Connection Pipe Diameter | Liquid | 19.05 mm |
| Gas | 41.27 mm | |
| Operation Range | Cooling | -5 to 52 °CDB |
| Heating | -20 to 21 °CDB | |
Scroll
- Note:
- Specifications are based on the following conditions.
- Cooling:
- Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
- Heating:
- Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
- Pipe length:
- 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
- *1
- Minimum connectable indoor unit number is 2.
- *2
- The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
- surrounding noise and reflections are received and the measured value is usually larger than the indicated value.
Dimensions
Outdoor Unit : AJY162LNLBH / AJY090LNLBH / AJY090LNLBH

GLOBAL | English