Heat Pump Modular Type V-II Series AJY432LALH [3Phase]
Features
- Excellent energy savings
- High design flexibility for various building air conditioning
- Easy installation and maintenanc
- Efficiency in actual operation
- Energy saving technology that boosted operation efficiency
Capacity
135.0 kW
150.0 kW
Specification
Rating Capacity Range | 48 |
---|---|
Maximum Connectable Indoor Unit*1 | 48 |
Indoor unit connectable capacity | 67.5 - 202.5 kW |
Scroll
Power source | Phase | 3-phase 4 wire |
---|---|---|
Voltage | 400 V | |
Frequency | 50 Hz | |
Capacity | Cooling | 135.0 kW |
Heating | 150.0 kW | |
Input Power | Cooling | 42.51 kW |
Heating | 37.80 kW | |
EER | Cooling | 3.18 W/W |
COP | Heating | 3.97 W/W |
Air Flow Rate | 13,000 × 3 m/³h | |
Sound Pressure Level*2 | Cooling | 66 dB(A) |
Heating | 66 dB(A) | |
Maximum external static pressure | 80 Pa | |
Compresor motor output | 3.9 × 3 + 4.5 × 3 kW | |
Heat exchanger fin | Blue fin | |
Net Dimensions | Height | 1,690 mm |
Width | 1,240 × 3 mm | |
Depth | 765 mm | |
Net Weight | 303 + 303 + 303 kg | |
Refrigerant | Type | R410A |
Global Warming Potential | 2,088 | |
Charge | 11.8 × 3 kg | |
Connection Pipe Diameter | Liquid | 19.05 mm |
Gas | 41.27 mm | |
Operation Range | Cooling | -5 to 46 °CDB |
Heating | -20 to 21 °CDB |
Scroll
- Note:
- Specifications are based on the following conditions.
- Cooling:
- Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
- Heating:
- Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
- Pipe length:
- 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
- When cooling operation will be conducted at outdoor air temperature below -5°C,
- the outdoor unit must be installed in a position that is higher than or equal to those of indoor units.
- *1
- Minimum connectable indoor unit number is 2.
- *2
- The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
- surrounding noise and reflections are received and the measured value is usually larger than the indicated value.