Heat Pump for Small Capacity Type J-III Series AJY054LBLAH
Features
- Outstanding efficiency in real-world operating conditions
- High EER* and COP* Energy Efficiency Ratio
- Advanced technologies for high efficiency
- Long piping length
- Nonstop operation during oil recovery
- Easy installation
Capacity
Specification
| Rated Capacity Range | 6 |
|---|---|
| Maximum Connectable Indoor Unit | 1 - 13 |
Scroll
| Power source | Phase | Single-phase |
|---|---|---|
| Voltage | ~230 V | |
| Frequency | 50 Hz | |
| Capacity | Cooling | 15.5 kW |
| Heating | 18.0 kW | |
| Input Power | Cooling | 4.18 kW |
| Heating | 4.26 kW | |
| EER | Cooling | 3.71 W/W |
| COP | Heating | 4.23 W/W |
| Air Flow Rate | 6,900 m³/h | |
| Sound Pressure Level | Cooling | 53 dB(A) |
| Heating | 55 dB(A) | |
| Sound Power Level | Cooling | 69 dB(A) |
| Heating | 71 dB(A) | |
| Heat exchanger fin | Blue fin | |
| Net Dimensions | Height | 1,334 mm |
| Width | 970 mm | |
| Depth | 370 mm | |
| Net Weight | 119 kg | |
| Refrigerant | Type | R410A |
| Global Warming Potential | 2,088 | |
| Charge | 5.3 kg | |
| Connection Pipe Diameter | Liquid | 9.52 mm |
| Gas | 19.05 mm | |
| Total pipe length | 180 m | |
| Max. height difference |
50 m
40 m |
|
| Operation Range | Cooling | -5 to 46 °CDB |
| Heating | -20 to 21 °CDB | |
Scroll
- Note:
- Specifications are based on the following conditions.
- Cooling:
- Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
- Heating:
- Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
- Pipe length:
- 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
- The protective function may work when using it outside the operation range.
Dimensions
Outdoor Unit : AJY054LBLAH

GLOBAL | English