Heat Recovery Modular Type VR-II Series AJY414GALH  [3Phase]

Outdoor unit

Outdoor Unit :
AJY144GALH
Outdoor Unit :
AJY144GALH
Outdoor Unit :
AJY126GALH
Download :
Catalogue

Features

  • Highly energy-efficient operation
  • Energy-saving technologies for boosting operational efficiency
  • Ideal heat-exchanging path control
  • Sophisticated operation control
  • Flexible piping connection
  • Flexible installation of an RB Unit

Capacity

Cooling  130.0 kW
Heating  145.0 kW


Specifications

Rated Capacity Range 46
Max. Number of Connectable Indoor Units*1 64
Connectable Capacity of Indoor Units 65.0 - 195.0 kW
Scroll
Power Source Phase 3-phase 4 wire
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 130.0 kW
Heating 145.0 kW
Input Power Cooling 38.56 kW
Heating 36.44 kW
EER Cooling 3.37 W/W
COP Heating 3.98 W/W
Airflow Rate 13,000×3 m³/h
Sound Pressure Level*2 Cooling 65 dB(A)
Heating 66 dB(A)
Sound Power Level Cooling 86 dB(A)
Heating 88 dB(A)
Max. External Static Pressure 80 Pa
Compressor Motor Output 11.0×2+7.5 kW
Heat Exchanger Fin Blue fin
Net Dimensions Height 1,690 mm
Width 1,240×3 mm
Depth 765 mm
Net Weight 286×3 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.8×3 kg
Connection Pipe Diameter Liquid 19.05 mm
Discharge Gas 34.92 mm
Suction Gas 41.27 mm
Operation Range Cooling -10 to 46 °CDB
Heating -20 to 21 °CDB
Cooling / Heating -10 to 21 °CDB
Scroll
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.

Dimensions

Outdoor Unit : AJY144GALH / AJY144GALH / AJY126GALH

Outdoor unit