Heat Recovery Modular Type VR-II Series AJY252GALH  [3Phase]

Outdoor unit

Outdoor Unit :
AJY144GALH
Outdoor Unit :
AJY108GALH
Download :
Catalogue

Features

  • Highly energy-efficient operation
  • Energy-saving technologies for boosting operational efficiency
  • Ideal heat-exchanging path control
  • Sophisticated operation control
  • Flexible piping connection
  • Flexible installation of an RB Unit

Capacity

Cooling  78.5 kW
Heating  87.5 kW


Specifications

Rated Capacity Range 28
Max. Number of Connectable Indoor Units*1 42
Connectable Capacity of Indoor Units 39.3 - 117.7 kW
Scroll
Power Source Phase 3-phase 4 wire
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 78.5 kW
Heating 87.5 kW
Input Power Cooling 23.36 kW
Heating 22.39 kW
EER Cooling 3.36 W/W
COP Heating 3.91 W/W
Airflow Rate 13,000+11,100 m³/h
Sound Pressure Level*2 Cooling 63 dB(A)
Heating 64 dB(A)
Sound Power Level Cooling 84 dB(A)
Heating 86 dB(A)
Max. External Static Pressure 80 Pa
Compressor Motor Output 11.0+7.5 kW
Heat Exchanger Fin Blue fin
Net Dimensions Height 1,690 mm
Width 1,240+930 mm
Depth 765 mm
Net Weight 286+262 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.8×2 kg
Connection Pipe Diameter Liquid 15.88 mm
Discharge Gas 28.58 mm
Suction Gas 34.92 mm
Operation Range Cooling -10 to 46 °CDB
Heating -20 to 21 °CDB
Cooling / Heating -10 to 21 °CDB
Scroll
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.

Dimensions

Outdoor Unit : AJY144GALH / AJY108GALH

Outdoor unit