High Static Pressure Duct  ARYG45LHTA

Indoor unit and Outdoor unit

i-PAM
Indoor Unit :
ARYG45LHTA
Outdoor Unit :
AOYG45LETL
Download :
Catalogue

Features

  • Greater energy efficiency
  • Design that produces high static pressure
  • Easy installation (compact and lightweight)
  • Low noise mode
  • Low ambient operation

Feature Icons

Economy mode: A thermostat setting is adjusted automatically according to the room temperature to avoid unnecessary cooling or heating. Auto changeover: The unit automatically switches between heating and cooling operations based on the set temperature and room temperature. Automatic fan speed: Microprocessor automatically adjusts the fan speed and airflow according to changes in room temperature. Auto restart: The unit automatically restarts in the previous operation mode when power returns after an outage. Weekly & Temperature setback timer: Sets temperature for two sets of On/Off times and for each day of the week. Filter sign: Indicates when the filter should be cleaned. Blue fin

Options

Setting temperature range limitation: Sets the minimum and maximum limits on room temperature to establish the right balance between energy saving and comfortable environment. Set temperature auto return: The set temperature automatically returns to the previous level. Low noise mode: Reduces the noise level of an outdoor unit. Fresh air intake: Fresh air can be taken in from outside by a fan connected to an external control unit. Auto-off timer: The unit automatically switches off when a predetermined time has elapsed after the timer is activated. External error output External On/Off input

Capacity

Cooling  12.5 kW
Heating  14.0 kW


Specifications

Power Source Phase Single-phase
Voltage 230 V
Frequency 50 Hz
Capacity Cooling 12.5 kW(4.5 - 14.0) kW
Heating 14.0 kW (5.0 - 16.2) kW
Input Power Cooling 4.30 kW
Heating 3.80 kW
EER Cooling 2.91 W/W
COP Heating 3.68 W/W
Max. Operating Current Cooling 22.5 A
Heating 22.5 A
Moisture Removal 1.5 I/h
Sound Pressure Level*2 Indoor (Cooling) High 47 dB(A)
Middle 43 dB(A)
Low 40 dB(A)
Quiet - dB(A)
Indoor (Heating) High 47 dB(A)
Middle 43 dB(A)
Low 40 dB(A)
Quiet - dB(A)
Sound Pressure Level*2 Outdoor (Cooling) High 55 dB(A)
Outdoor (Heating) High 55 dB(A)
Airflow Rate Indoor High 3350 m3/h
Outdoor High 6750 m3/h
Static Pressure Range (standard) 100 to 250 (100) Pa
Net Dimensions
Indoor
Height 400 mm
Width 1050 mm
Depth 500 mm
Net Dimensions
Outdoor
Height 1290 mm
Width 900 mm
Depth 330 mm
Net Weight Indoor 46 kg (101 lbs)
Outdoor 86 kg (189 lbs)
Connection Pipe Diameter Liquid 9.52 mm
Gas 15.88 mm
Drain Hose Diameter Indoor 23.4 mm
Outdoor 25.4 mm
Max. Pipe Length (Pre Charge) 50 (20) m
Max. Height Difference 30 m
Operation Range Cooling -15 to 46 °C DB
Heating -15 to 24 °C DB
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 3,350 g
Scroll

Dimensions

Indoor Unit : ARYG45LHTA

Indoor unit

Optional Parts

Wired Remote Controller
UTY-RVNYM
Simple Remote Controller
UTY-RSNYM
Long-life Filter
UTD-LF60KA
Remote Sensor Unit
UTY-XSZX