Heat Pump for Small Capacity Type J-IVS Series AJY045LCLBH

Outdoor unit

Outdoor Unit :
AJY045LCLBH
Download :
Catalogues

Features

  • It Can be Easily Positioned and Installed
  • Small and light weight outdoor unit
  • Low sound level design
  • Long piping length
  • Up to 13 units* can be connected

Capacity

Cooling   14.0 kW
Heating   14.0 kW (Nominal) / 16.0 kW (Max)


Specification

Rated Capacity Range 5 HP
Maximum Connectable Indoor Unit 1 - 12
Indoor unit connectable capacity 7.0 - 18.2 kW
Scroll
Power source Phase Single-phase 1
Voltage 230 V
Frequency 50 Hz
Capacity Cooling 14.0 kW
Nominal Heating 14.0 kW
Max Heating 16.0 kW
Input Power Cooling 4.43 kW
Heating 3.11 kW
Nominal Heating 3.11 kW
Max Heating 3.93 kW
EER Cooling 3.16 W/W
COP Nominal Heating 4.51 W/W
Max Heating 4.07 W/W
Air Flow Rate 4200 m³/h
Sound Pressure Level*2 Cooling 53 dB(A)
Heating 56 dB(A)
Sound Power Level Cooling 69 dB(A)
Heating 69 dB(A)
Max. External Static Pressure 25 Pa
Compressor Motor Output 2.1 kW
Heat exchanger fin Blue fin
Net Dimensions Height 998 mm
Width 970 mm
Depth 370 mm
Net Weight 86 kg
Refrigerant Type R410A
Global Warming Potential 2088
Charge 4.0 kg (8.4 CO2eq–T)
Connection Pipe Diameter Liquid φ9.52 mm
Gas φ15.88 mm
Total pipe length 80 m
Max. height difference
(Outdoor Unit: Upper/Lower)
30 / 30 m
Operation Range Cooling -5 to 46 °CDB
Heating -20 to 21 °CDB
Scroll
Note:
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating:
Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length:
7.5 m; Height difference between outdoor unit and indoor unit : 0 m. The protective function may work when using it outside the operation range.

Dimensions

Outdoor Unit : AJY045LCLBH

Outdoor unit