Heat Pump Modular type V-III TROPICAL Series AJY378LNLBHH  [3Phase]

Outdoor unit

Outdoor Unit :
AJY126LNLBH
Outdoor Unit :
AJY126LNLBH
Outdoor Unit :
AJY126LNLBH
Download :
Catalogue

Features

  • Excellent energy saving
  • Great design flexibility for placement in any building
  • Easy installation and maintenance
  • Energy-saving technologies for boosting operational efficiency
  • Thorough anti-corrosion treatment
  • Outstanding cooling capacity

Capacity

Cooling  120.0 kW
Heating  135.0 kW

Specification

Rated Capacity Range 42
Maximum Connectable Indoor Unit 55
Indoor unit connectable capacity 60 - 156 kW
Scroll
Power source Phase 3-phase
Voltage ~400 V
Frequency 50,60 Hz
Capacity Cooling 120.0 kW
Heating 135.0 kW
Input Power Cooling 32.88 kW
Heating 33.51 kW
EER Cooling 3.65 W/W
COP Heating 4.03 W/W
Air Flow Rate 13000×3 m³/h
Sound Pressure Level Cooling 65 dB(A)
Heating 67 dB(A)
Sound Power Level Cooling 88 dB(A)
Heating 89 dB(A)
Max. External Static Pressure 82 Pa
Compressor Motor Output 11.0×3 kW
Heat exchanger fin Blue fin
Net Dimensions Height 1690×3 mm
Width 1240×3 mm
Depth 765×3 mm
Net Weight 279×3 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.8×3 kg
Connection Pipe Diameter Liquid 19.05 mm
Gas 41.27 mm
Operation Range Cooling -5 to 46 °CDB
Heating -20 to 21 °CDB
Scroll
Note:
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating:
Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length:
7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.

Dimensions

Outdoor Unit : AJY126LNLBH / AJY126LNLBH / AJY126LNLBH

Outdoor unit