Heat Recovery Modular Type VR-II Series AJH432GALH

Outdoor unit

Outdoor Unit :
AJH144GALH
Outdoor Unit :
AJH144GALH
Outdoor Unit :
AJH144GALH
Download :
Catalogues

Features

  • Highly energy-efficient operation
  • Energy-saving technologies for boosting operational efficiency
  • Ideal heat-exchanging path control
  • Sophisticated operation control
  • Flexible piping connection
  • Flexible installation of an RB Unit

Capacity

Cooling  135.0 kW
Heating  150.0 kW


Specifications

Rated Capacity Range 48
Max. Number of Connectable Indoor Units*1 64
Connectable Capacity of Indoor Units 67.5 - 202.5 kW
Scroll
Power Source Phase 3 phase 4 wire
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 135.0 kW
Heating 150.0 kW
Input Power Cooling 40.83 kW
Heating 38.31 kW
EER Cooling 3.31 W/W
COP Heating 3.92 W/W
Airflow Rate 13,000×3 m³/h
Sound Pressure Level*2 Cooling 66 dB(A)
Heating 66 dB(A)
Sound Power Level Cooling 87 dB(A)
Heating 88 dB(A)
Max. External Static Pressure 80 Pa
Compressor Motor Output 11.0×3 kW
Heat Exchanger Fin Blue fin
Net Dimensions Height 1,690 mm
Width 1,240×3 mm
Depth 765 mm
Net Weight 286×3 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.8×3 kg
Connection Pipe Diameter Liquid 19.05 mm
Discharge Gas 34.92 mm
Suction Gas 41.27 mm
Operation Range Cooling -10 to 46 °CDB
Heating -20 to 21 °CDB
Cooling / Heating -10 to 21 °CDB
Scroll
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.

Dimensions

Outdoor Unit : AJH144GALH / AJH144GALH / AJH144GALH

Outdoor unit