Economy mode : Thermostat setting automatically changes according to the temperature to avoid unnecessary cooling and heating. Auto-changeover : The unit automatically switches between heating and cooling modes based on your temperature setting and the room temperature. Automatic fan speed : The micro-computer automatically adjusts the airflow effectively to follow the changes of room temperature. Auto restart : In the event of a temporary power failure, the air conditioner will automatically restart in the same operating mode as before, once power supply is restored. Connectable fresh air duct : Outside air can be introduced by attaching field supplied duct to fresh air knockout and optional part. Connectable distributing duct : Systems are capable of attaching field-supplied branch ducts distributing the airflow. Weekly + setback timer : Weekly + Setback timer can set temperature for two times spans and for each day of the week. Filter sign : Indicates the filter cleaning period by lamp. Blue fin

Capacity

Cooling   12.1 kW
Heating   13.5 kW


Specification

Power source Phase Single-phase
Voltage 230 V
Frequency 50 Hz
Capacity Cooling 12.1 (4.0 - 13.0) kW
Heating 13.5 (4.2 - 15.2) kW
Input Power Cooling 4.220 kW
Heating 3.840 kW
EER Cooling 2.87 W/W
COP Heating 3.52 W/W
Pdesign Cooling 12.1 kW
SEER Cooling 5.25 W/W
Max. Operating Current Cooling 28.5 A
Heating 28.5 A
Moisture Removal 4.0 l/h
Sound Pressure Level Indoor (Cooling) High 42 dB(A)
Middle 38 dB(A)
Low 32 dB(A)
Quiet 28 dB(A)
Indoor (Heating) High 42 dB(A)
Middle 38 dB(A)
Low 32 dB(A)
Quiet 28 dB(A)
Sound Pressure Level Outdoor (Cooling) High 57 dB(A)
Outdoor (Heating) High 57 dB(A)
Sound Power Level Indoor (Cooling) High 68 dB(A)
Indoor (Heating) High 70 dB(A)
Outdoor (Cooling) High 71 dB(A)
Outdoor (Heating) High 71 dB(A)
Air Flow Rate Indoor (Cooling) High 2100 m3/h
Outdoor (Cooling) High 4450 m3/h
Static pressure range (Standard) 30 - 150 (60) Pa
Net Dimensions
Indoor
Height 270 mm
Width 1135 mm
Depth 700 mm
Net Dimensions
Outdoor
Height 998 mm
Width 940 mm
Depth 320 mm
Net Weight Indoor 39.0 kg
Outdoor 67.0 kg
Connection Pipe Diameter Liquid φ9.52 mm
Gas φ15.88 mm
Max Pipe Length (Pre Charge) 50 (30.0) m
Max Height Difference 30 m
Operation Range Cooling -15 to 46 °CDB
Heating -15 to 24 °CDB
Refrigerant Type R32
Global Warming Potential 675
Charge 2700 g (1.823 CO2eq–T)