Halcyon™ MULTI-ROOM MINI-SPLIT SYSTEMS Flex Zone (2 to 8 Zones) AOU48RLXFZ1

Halcyon™ Hybrid Flex Inverter

Outdoor Unit : AOU48RLXFZ1

Outdoor Unit :
AOU48RLXFZ1
Downloads :
Manuals
Warranty

  • Individual Zoning
  • Inverter Technology
  • Inverter control
  • 130% Connectable Capacity
  • Cassette Model Fits Into Standard Ceiling Tile
  • Central Remote Control (Optional Accessory Part #UTY-DMMUM)
  • Hidden or Showcased Indoor Unit
  • Stable and comfortable
Cooling  48,000 BTU/h
Heating  54,000 BTU/h

Specification
Power Source Voltage/Frequency/Phase 208-230/60/1
Connectable Indoor Unit Number 2 to 8
Connectable Indoor Unit Capacity BTU/h 80 to 130% Nominal
(39,000 - 62,000 BTU)
Connectable Branch Box Number 1 to 3
Cooling Nominal BTU/h 48,000
Max 51,100
Heating Nominal BTU/h 54,000
Low Temp. 40,000
Max 57,000
Operation Range Cooling °F(°C) 23-115 (-5-46)
Heating 5-75 (-15-24)
Input Power:
Rated
Cooling kW 5.52 / 5.19 / 5.35
Heating 5.02 / 4.89 / 4.96
Current:
Outdoor Max.
Cooling A 24.5 / 23.0 / 23.7
Heating 22.3 / 21.7 / 22.0
MAX.CRT.BKR A 40
Outdoor Fan Speed RPM Clg/Htg 890/910
Fan: Type × Quantity Propeller × 1
Fan Motor Output W 111
Sound Pressure Level Cooling dB(A) 56
Heating 58
Max. Pipe Length Total Ft (m) 377 (115)
Between Box &
Farthest Indoor Unit
Ft (m) 49 (15)
Max. Pipe Height Difference Between
Outdoor Unit & Branch Box
Ft (m) 98 (30)
Difference
Between Indoor Units
Ft (m) 98 (30)
Difference Between
Outdoor Unit & Farthest Indoor
Ft (m) 98 (30)
Connection Method Flare
Conn. Pipe Diameter Inch 3/8 (Liq.) 5/8 (Suc.)
Net Weight lbs. (kg) 216 (98)
Dimensions Height Inch 36
mm 914
Width Inch 38-1/4
mm 970
Depth Inch 14-5/8
mm 370
Refrigerant (Global Warming Potential) R410A
Scroll
Dimensions

Outdoor Unit : AOU48RLXFZ1

Outdoor Units - Dimensions