Heat Recovery Modular Type VR-II Series AJY306GALH  [3Phase]

Outdoor unit

Outdoor Unit :
AJY108GALH
Outdoor Unit :
AJY108GALH
Outdoor Unit :
AJYA90GALH
Download :
Catalogue

Features

  • Highly energy-efficient operation
  • Energy-saving technologies for boosting operational efficiency
  • Ideal heat-exchanging path control
  • Sophisticated operation control
  • Flexible piping connection
  • Flexible installation of an RB Unit

Capacity

Cooling  95.0 kW
Heating  106.5 kW


Specifications

Rated Capacity Range 34
Max. Number of Connectable Indoor Units*1 50
Connectable Capacity of Indoor Units 47.5 - 142.5 kW
Scroll
Power Source Phase 3-phase 4 wire
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 95.0 kW
Heating 106.5 kW
Input Power Cooling 26.61 kW
Heating 26.57 kW
EER Cooling 3.57 W/W
COP Heating 4.01 W/W
Airflow Rate 11,100×3 m³/h
Sound Pressure Level*2 Cooling 63 dB(A)
Heating 65 dB(A)
Sound Power Level Cooling 85 dB(A)
Heating 87.2 dB(A)
Max. External Static Pressure 80 Pa
Compressor Motor Output 7.5×3 kW
Heat Exchanger Fin Blue fin
Net Dimensions Height 1,690 mm
Width 930×3 mm
Depth 765 mm
Net Weight 286×3 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.8×3 kg
Connection Pipe Diameter Liquid 19.05 mm
Discharge Gas 28.58 mm
Suction Gas 34.92 mm
Operation Range Cooling -10 to 46 °CDB
Heating -20 to 21 °CDB
Cooling / Heating -10 to 21 °CDB
Scroll
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.

Dimensions

Outdoor Unit : AJY108GALH / AJY108GALH / AJYA90GALH

Outdoor unit