High Static Pressure Duct  ARYG45LHTA

Indoor unit and Outdoor unit

i-PAM
Indoor Unit :
ARYG45LHTA
Outdoor Unit :
AOYG45LETL
Download :
Catalogue

Features

  • Greater energy efficiency
  • Design that produces high static pressure
  • Easy installation (compact and lightweight)
  • Low noise mode
  • Low ambient operation

Feature Icons

Economy mode: A thermostat setting is adjusted automatically according to the room temperature to avoid unnecessary cooling or heating. Auto changeover: The unit automatically switches between heating and cooling modes based on the temperature setting and the room temperature. Automatic fan speed: A micro-computer automatically adjusts the airflow to follow the changes in room temperature. Auto restart: In the event of a temporary power failure, the air conditioner will automatically restart in the same operating mode as before, once the power supply is restored. Weekly & Temperature setback timer: Weekly & Temperature setback timer can set the temperature for 2-time spans and for each day of the week. Filter sign: Indicates the filter cleaning period by blinking. Blue fin

Options

Setting temperature range limitation: Sets the minimum and maximum limits on room temperature to establish the right balance between energy saving and a comfortable environment. Set temperature auto return: The setting temperature automatically returns to the previously set temperature. Low noise mode: Reduces the noise level of an outdoor unit. Fresh air intake: Fresh air can be taken in by a fan connected to an external control unit. Auto-off timer: Automatically stops operation when a fixed time has elapsed from the start of operation. External error output External ON/OFF input Special Cooling: Special Cooling

Capacity

Cooling  12.5 kW
Heating  14.0 kW


Specifications

Power Source Phase Single-phase
Voltage 230 V
Frequency 50 Hz
Capacity Cooling 12.5 kW(4.5 - 14.0) kW
Heating 14.0 kW (5.0 - 16.2) kW
Input Power Cooling 4.30 kW
Heating 3.80 kW
EER Cooling 2.91 W/W
COP Heating 3.68 W/W
Max. Operating Current Cooling 22.5 A
Heating 22.5 A
Moisture Removal 1.5 I/h
Sound Pressure Level*2 Indoor (Cooling) High 47 dB(A)
Middle 43 dB(A)
Low 40 dB(A)
Quiet - dB(A)
Indoor (Heating) High 47 dB(A)
Middle 43 dB(A)
Low 40 dB(A)
Quiet - dB(A)
Sound Pressure Level*2 Outdoor (Cooling) High 55 dB(A)
Outdoor (Heating) High 55 dB(A)
Airflow Rate Indoor High 3350 m3/h
Outdoor High 6750 m3/h
Static Pressure Range (standard) 100 to 250 (100) Pa
Net Dimensions
Indoor
Height 400 mm
Width 1050 mm
Depth 500 mm
Net Dimensions
Outdoor
Height 1290 mm
Width 900 mm
Depth 330 mm
Net Weight Indoor 46 kg (101 lbs)
Outdoor 86 kg (189 lbs)
Connection Pipe Diameter Liquid 9.52 mm
Gas 15.88 mm
Drain Hose Diameter Indoor 23.4 mm
Outdoor 25.4 mm
Max. Pipe Length (Pre Charge) 50 (20) m
Max. Height Difference 30 m
Operation Range Cooling -15 to 46 °C DB
Heating -15 to 24 °C DB
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 3,350 g
Scroll

Dimensions

Indoor Unit : ARYG45LHTA

Indoor unit

Optional Parts

Wired Remote Controller
UTY-RVNYM
Simple Remote Controller
UTY-RSNYM
Long-life Filter
UTD-LF60KA
Remote Sensor Unit
UTY-XSZX