Slim Duct ARXD14GALH

Indoor unit

Indoor Unit :
ARXD14GALH
Download :
Catalogue

Capacity

Cooling  4.5 kW
Heating  5.0 kW

Specification

Power source Phase Single-phase
Voltage ~230 V
Frequency 50 Hz
Capacity Cooling 4.5 kW
Heating 5.0 kW
Input Power 92 W
Air Flow Rate High 800 m3/h
Middle 710 m3/h
Low 610 m3/h
Static pressure range 0 to 90 Pa
Standard static pressure 25 Pa
Sound Pressure Level High 34 dB(A)
Middle 32 dB(A)
Low 28 dB(A)
Net Dimensions Height 198 mm
Width 700 mm
Depth 620 mm
Net Weight 18 kg (40 lbs)
Connection Pipe Diameter Liquid (Flare) 6.35 mm
Gas (Flare) 12.70 mm
Drain Hose Diameter Indoor 25 mm
Outdoor 32 mm
Scroll
Note:
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 27˚CDB / 19˚CWB, and outdoor temperature of 35˚CDB / 24˚CWB.
Heating:
Indoor temperature of 20˚CDB / (15˚CWB), and outdoor temperature of 7˚CDB / 6˚CWB.
Pipe length:
7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
Voltage:
230 [V].

Dimensions

Indoor Unit : ARXD14GALH

Indoor unit