Main contents starts here.
UTZ-BX080A Specifications
| Rated flow rate |
800 m3/h |
| Model No. |
UTZ-BX080A |
| Power source |
220-240V , 50Hz |
| HEAT EXCHANGE VENTILATION |
Input power |
(Extra high)/High/Low |
W |
347 / 309 / 302 |
| Air flow rate |
(Extra high)/High/Low |
m3/h |
800 / 800 / 650 |
| External static pressure |
(Extra high)/High/Low |
Pa |
140 / 110 / 70 |
| Temperature Exchange Efficiency |
(Extra high)/High/Low |
% |
75 / 75 / 76 |
| Energy Exchange Efficiency Cooling |
(Extra high)/High/Low |
% |
65 / 65 / 68 |
| Energy Exchange Efficiency Heat pump |
(Extra high)/High/Low |
% |
71 / 71 / 74 |
| Sound pressure level |
(Extra high)/High/Low |
dB* |
38 / 36.5 / 32 |
| NORMAL VENTILATION |
Input power |
(Extra high)/High/Low |
W |
337 / 300 / 297 |
| Air flow rate |
(Extra high)/High/Low |
m3/h |
800 / 800 / 650 |
| External static pressure |
(Extra high)/High/Low |
Pa |
140 / 110 / 70 |
| Sound pressure level |
(Extra high)/High/Low |
dB* |
38.5 / 37 / 33 |
| Dimensions |
W×D×H |
mm |
1,322×884×388 |
| Weight |
kg |
71 |
| Outlet duct diameter |
mm |
250 |
| Operation range |
ºC |
-10 to 40 |
| Maximum humidity |
% |
85 |
* The noise level must be measured 1.5 m below the centre of the unit.