Main contents starts here.
UTZ-BX050A Specifications
| Rated flow rate |
500 m3/h |
| Model No. |
UTZ-BX050A |
| Power source |
220-240V , 50Hz |
| HEAT EXCHANGE VENTILATION |
Input power |
(Extra high)/High/Low |
W |
214 / 169 / 151 |
| Air flow rate |
(Extra high)/High/Low |
m3/h |
500 / 500 / 370 |
| External static pressure |
(Extra high)/High/Low |
Pa |
105 / 70 / 38 |
| Temperature Exchange Efficiency |
(Extra high)/High/Low |
% |
75 / 75 / 77 |
| Energy Exchange Efficiency Cooling |
(Extra high)/High/Low |
% |
62 / 62 / 67 |
| Energy Exchange Efficiency Heat pump |
(Extra high)/High/Low |
% |
67 / 67 / 71 |
| Sound pressure level |
(Extra high)/High/Low |
dB* |
34 / 31 / 25 |
| NORMAL VENTILATION |
Input power |
(Extra high)/High/Low |
W |
210 / 161 / 145 |
| Air flow rate |
(Extra high)/High/Low |
m3/h |
500 / 500 / 370 |
| External static pressure |
(Extra high)/High/Low |
Pa |
105 / 70 / 38 |
| Sound pressure level |
(Extra high)/High/Low |
dB* |
34 / 32 / 26.5 |
| Dimensions |
W×D×H |
mm |
962×904×270 |
| Weight |
kg |
43 |
| Outlet duct diameter |
mm |
200 |
| Operation range |
ºC |
-10 to 40 |
| Maximum humidity |
% |
85 |
* The noise level must be measured 1.5 m below the centre of the unit.