AIRSTAGE VRF System (Air Conditioners)

UTZ-BX025A Specifications

Rated flow rate 250 m3/h
Model No. UTZ-BX025A
Power source 220-240V , 50Hz
HEAT EXCHANGE VENTILATION Input power (Extra high)/High/Low W 119 / 99 / 79
Air flow rate (Extra high)/High/Low m3/h 250 / 250 / 170
External static pressure (Extra high)/High/Low Pa 90 / 80 / 37
Temperature Exchange Efficiency (Extra high)/High/Low % 75 / 75 / 77
Energy Exchange Efficiency Cooling (Extra high)/High/Low % 63 / 63 / 66
Energy Exchange Efficiency Heat pump (Extra high)/High/Low % 70 / 70 / 73
Sound pressure level (Extra high)/High/Low dB* 28 / 26 / 21
NORMAL VENTILATION Input power (Extra high)/High/Low W 119 / 98 / 79
Air flow rate (Extra high)/High/Low m3/h 250 / 250 / 170
External static pressure (Extra high)/High/Low Pa 90 / 80 / 37
Sound pressure level (Extra high)/High/Low dB* 27 / 26.5 / 21.5
Dimensions W×D×H mm 882×599×270
Weight kg 29
Outlet duct diameter mm 150
Operation range ºC -10 to 40
Maximum humidity % 85

* The noise level must be measured 1.5 m below the centre of the unit.

 

Top of Page