Main contents starts here.
UTZ-BX025A Specifications
| Rated flow rate |
250 m3/h |
| Model No. |
UTZ-BX025A |
| Power source |
220-240V , 50Hz |
| HEAT EXCHANGE VENTILATION |
Input power |
(Extra high)/High/Low |
W |
119 / 99 / 79 |
| Air flow rate |
(Extra high)/High/Low |
m3/h |
250 / 250 / 170 |
| External static pressure |
(Extra high)/High/Low |
Pa |
90 / 80 / 37 |
| Temperature Exchange Efficiency |
(Extra high)/High/Low |
% |
75 / 75 / 77 |
| Energy Exchange Efficiency Cooling |
(Extra high)/High/Low |
% |
63 / 63 / 66 |
| Energy Exchange Efficiency Heat pump |
(Extra high)/High/Low |
% |
70 / 70 / 73 |
| Sound pressure level |
(Extra high)/High/Low |
dB* |
28 / 26 / 21 |
| NORMAL VENTILATION |
Input power |
(Extra high)/High/Low |
W |
119 / 98 / 79 |
| Air flow rate |
(Extra high)/High/Low |
m3/h |
250 / 250 / 170 |
| External static pressure |
(Extra high)/High/Low |
Pa |
90 / 80 / 37 |
| Sound pressure level |
(Extra high)/High/Low |
dB* |
27 / 26.5 / 21.5 |
| Dimensions |
W×D×H |
mm |
882×599×270 |
| Weight |
kg |
29 |
| Outlet duct diameter |
mm |
150 |
| Operation range |
ºC |
-10 to 40 |
| Maximum humidity |
% |
85 |
* The noise level must be measured 1.5 m below the centre of the unit.