High Static Pressure Duct ARYG60LHTA  [3Phase]

Indoor unit and Outdoor unit

ALL DC
Indoor Unit :
ARYG60LHTA
Outdoor Unit :
AOYG60LATT
Download :
Catalogue

Features

  • High energy efficiency
  • Design also corresponding to high static pressure
  • Easy installation (Compact size & Lightweight)
  • Low noise
  • Low ambient operation

Feature Explanation Icons

Economy mode : Thermostat setting automatically changes according to the temperature to avoid unnecessary cooling and heating. Auto-changeover : The unit automatically switches between heating and cooling modes based on your temperature setting and the room temperature. Automatic fan speed : The micro-computer automatically adjusts the airflow effectively to follow the changes of room temperature. Auto restart : In the event of a temporary power failure, the air conditioner will automatically restart in the same operating mode as before, once power supply is restored. Weekly + setback timer : Weekly + Setback timer can set temperature for two times spans and for each day of the week. Filter sign : Indicates the filter cleaning period by lamp. Blue fin

Options

Room temperature set point limitation : The minimum and maximum temperature range can be set giving further energy saving while considering the comfort of the occupants. Set temperature auto return : The setting temperature automatically returns to the previously set temperature. 10°C HEAT operation : The room temperature can be set to go no lower than 10°C, thus ensuring that the room does not get too cold when not occupied. Low noise mode : Sound noise level of outdoor unit can be selected. Fresh air intake : Fresh air can be taken in by a fan which can be connected using external control unit. Auto off timer : Automatically stops operation when a fixed time has elapsed from the start of operation. Sleep timer : The micro-computer gradually changes the room temperature automatically to afford a comfortable night's sleep. Program timer : This digital timer allows selection of one of four options : ON, OFF, ON;→OFF or OFF→ON. External error output External ON/OFF input

Capacity

Cooling  15.0 kW
Heating  18.0 kW


Specification

Power source Phase 3-phase
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 15.0 kW(6.2 - 17.5) kW
Heating 18.0 kW (6.2 - 20.0) kW
Input Power Cooling 4.70 kW
Heating 5.15 kW
COP Heating 3.50 W/W
Max. Operating Current Cooling 12.5 A
Heating 12.5 A
Moisture Removal 2.0 I/h
Sound Pressure Level Indoor (Cooling) High 45 dB(A)
Middle 40 dB(A)
Low 36 dB(A)
Quiet - dB(A)
Indoor (Heating) High 45 dB(A)
Middle 40 dB(A)
Low 36 dB(A)
Quiet - dB(A)
Sound Pressure Level Outdoor (Cooling) High 56 dB(A)
Outdoor (Heating) High 58 dB(A)
Air Flow Rate Indoor High 3550 m3/h
Outdoor High 6900 m3/h
Static pressure range (Standard) 60 to 260 (60) Pa
Net Dimensions
Indoor
Height 425 mm
Width 1250 mm
Depth 490 mm
Net Dimensions
Outdoor
Height 1290 mm
Width 900 mm
Depth 330 mm
Net Weight Indoor 54 kg (119 lbs)
Outdoor 104 kg (229 lbs)
Connection Pipe Diameter Liquid 9.52 mm
Gas 15.88 mm
Drain Hose Diameter Indoor 23.4 mm
Outdoor 25.4 mm
Max Pipe Length (Pre Charge) 75 (30) m
Max Height Difference 30 m
Operation Range Cooling -15 to 46 °CDB
Heating -15 to 24 °CDB
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 3,450 g
Scroll

Dimensions

Indoor Unit : ARYG60LHTA

Indoor unit

Optional Parts

Wired Remote Controller
UTY-RNNYM
Wired Remote Controller
UTY-RVNYM
Simple Remote Controller
UTY-RSNYM
Remote Sensor Unit
UTY-XSZX
IR Receiver Kit
UTY-LRHYM